Viessmann · Boiler troubleshooting
Wire call-for-heat input lH
What is going on
lH is an optional normally open dry contact that can give a call for heat, block the boiler, or trigger a DHW recirculation pump run.
Check in this order
- Use a normally open contact only.
- Set the function in the commissioning assistant.
- Note contact closed will start a call for heat or block, depending on setting.
- For DHW recirculation pump demand, the pump runs for 5 minutes per pulse.
Applies to: lH plug
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 200 CI2 Installation Instructions, p. 26. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.