Viessmann · Boiler troubleshooting

Checking the flue gas temperature sensor

Vitocrossal 300 CU3A

What is going on

The flue gas temperature sensor locks out the boiler when the permissible flue gas temperature is exceeded. The interlock must be reset after the flue system has cooled down.

Likely causes

  • Flue gas temperature above permissible limit
  • Faulty flue gas temperature sensor

Check in this order

  1. Let the flue system cool down.
  2. Pull the leads from flue gas temperature sensor A.
  3. Measure the sensor resistance and compare it with the curve.
  4. Replace the sensor if the deviation is severe.
  5. Press reset button R to clear the interlock.

Applies to: Vitocrossal 300 CU3A 26 to 199

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 300 CU3A 26 to 199 Service Instructions, p. 95. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.