Burner reassembly and final combustion check

Vitocrossal 300 CA3B

What is going on

Reassembly torques and the required combustion check after burner work.

Check in this order

  1. Position the burner plate with burner mesh assembly on the 8 studs on the boiler section. Tighten nuts to 7.3 lb.ft (10 Nm).
  2. Position the upper burner section above the burner plate. Tighten the M10 nuts to 7.3 lb.ft (10 Nm).
  3. Push on the ignition and ionization electrode connectors.
  4. Insert connectors at the plug-in panel and at the burner control unit. Insert the mains plug last.
  5. Fit the gas connection pipe.
  6. Check the fitting for gas tightness. Do not use leak detection spray near electrical contacts.
  7. Start the burner and carry out a function test.
  8. Take a CO2 reading after each burner dismantling, per the items on pp. 67 and 68.
  9. Record the readings in the maintenance record on p. 162.

Applies to: Vitocrossal 300 CA3B Series 2.5 to 6.0

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann Vitocrossal 300 CA3B service instructions, p. 75. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.