Viessmann · Boiler troubleshooting
Safety relief valve and discharge pipe installation
What is going on
Install the factory-supplied pressure relief valve and its discharge piping so it cannot scald people or trap pressure.
Check in this order
- Use the approved factory-supplied pressure relief valve.
- Apply pipe sealant to both ends of the pipe fittings and install onto the tees.
- Install the pressure relief valve and the isolation valve for the drain connection, then tighten.
- Do not install any isolation valve between the boiler and the pressure relief valve.
- Route the discharge pipe to a floor drain, ending about 6 in. (150 mm) above the drain.
- Keep the discharge pipe end unthreaded, do not reduce its diameter, and do not install a shutoff valve in it.
- Orient the discharge to prevent scalding. Never pipe it outdoors.
Applies to: Vitodens 200-W B2HA 45, 60
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitodens 200-W B2HA 45, 60 installation instructions, p. 29. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.