Wire the system supply and return sensors
What is going on
Two strap-on sensors are required for proper control. If the return reads hotter than the supply, the control reports a sensor fault.
Likely causes
- Sensor not installed or installed incorrectly
- Return temperature reads above supply temperature
Check in this order
- Strap one sensor to the system supply piping and one to the return piping.
- Place the supply sensor at least six pipe diameters, and no more than 3 feet, downstream from the boiler connection to the main.
- Use immersion sensors on piping larger than 5 in. diameter or on nonmetallic piping for faster response.
- Wire the supply sensor to P14 pins 1 and 2, and the return sensor to P14 pins 3 and 2.
- Thermostat wire can be used for these sensors.
Applies to: SlimFit 550/750 Series 3 boiler
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SlimFit Series 3 boiler manual, p. 53. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.