Wire the system supply and return sensors

SlimFit Series 3

What is going on

Two strap-on sensors are required for proper control. If the return reads hotter than the supply, the control reports a sensor fault.

Likely causes

  • Sensor not installed or installed incorrectly
  • Return temperature reads above supply temperature

Check in this order

  1. Strap one sensor to the system supply piping and one to the return piping.
  2. Place the supply sensor at least six pipe diameters, and no more than 3 feet, downstream from the boiler connection to the main.
  3. Use immersion sensors on piping larger than 5 in. diameter or on nonmetallic piping for faster response.
  4. Wire the supply sensor to P14 pins 1 and 2, and the return sensor to P14 pins 3 and 2.
  5. Thermostat wire can be used for these sensors.

Applies to: SlimFit 550/750 Series 3 boiler

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SlimFit Series 3 boiler manual, p. 53. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.