Wiring multiple zones (EG water boilers)
What is going on
Zone valves or circulators can be used for multiple zones. Each zone needs its own power and control wiring as shown in the wiring diagram. Zoning with circulators needs a relay for each circulator.
Check in this order
- Power 3-wire zone valves from a separate transformer. The boiler does not supply that power.
- For circulator zoning, fit one relay per circulator and wire each relay to the matching CH or DHW terminals.
- Do not wire 3-wire zone valve end switches directly to the boiler T-T terminals.
- Wire each zone valve end switch to an isolation relay coil, then wire the isolation relay contact across the boiler T-T terminals.
- Follow the zone valve manufacturer's literature for valve wiring and application.
Applies to: EG water boilers with Unity-CI control
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: EG / PEG Series 7 boiler manual, p. 32. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.