Weil-McLain · Boiler troubleshooting
No display and no response to call for heat
What is going on
Control is not receiving 24 V power.
Likely causes
- Wiring short or incorrect wiring
- Blown 3 A low voltage fuse
- Transformer not connected correctly or not outputting 24 Vac
Check in this order
- Check wiring for shorts or errors and correct per wiring diagram, including transformer connection to the control.
- Check the 3 A low voltage fuse on the control.
- Replace a blown fuse with the proper part. If it blows again, recheck wiring.
- Check transformer connection and confirm 24 Vac output.
- Replace the transformer if it receives 120 Vac but does not output 24 Vac.
Applies to: SVF 500/600 Series 1
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SVF 500/600 Series 1 Boiler Manual, p. 124. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.