Viessmann · Boiler troubleshooting
Wiring the room controller to Viessmann Vitodens 100-W, WB1B
What is going on
The OT communication wires go to the 6-pole terminal block harness. The outdoor sensor can be wired either to the boiler 6-pole connector or to terminals 5 and 6 on the controller. The OT wires are not polarity sensitive.
Check in this order
- Refer to the boiler manual and remove the boiler cover.
- Find the wiring harness with the 6-pole terminal block.
- Find the wire marker for terminal 1.
- If the outdoor sensor is not yet installed, wire it to the 6-pole connector on the boiler or to terminals 5 and 6 on the controller.
- Connect the controller to terminals 1 and 2 of the 6-pole terminal block on the Vitodens 100-W WB1B.
- Terminate the OT wires at the controller sub-base on terminals 1 and 2.
Applies to: Vitodens 100-W WB1B
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Versatronik COMO OT manual, p. 11. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.