Weil-McLain · Boiler troubleshooting

Check flue gas temperature

SVF Series 1

What is going on

Flue temperature check at high fire.

Likely causes

  • Heat exchanger fouled

Check in this order

  1. Set the boiler to high fire.
  2. On the control display, view flue gas temperature and boiler return temperature.
  3. Flue gas should be no more than 30°F above boiler return temperature.
  4. If higher, shut down, let the boiler cool, and clean the heat exchanger (page 108).

Applies to: SVF 1500-3000 Series 1 boiler

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain SVF Series 1 boiler manual, p. 98. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.