Weil-McLain · Boiler troubleshooting
Code compliance and venting basics
What is going on
Venting and combustion air piping must meet the Air for Combustion and Ventilation provisions of NFPA 54 (ANSI Z223.1) or CSA B149.1 sections 8.2 to 8.4, plus local codes. Each boiler must have its own vent; never common-vent with other appliances.
Check in this order
- Never common-vent the SVF boiler with another boiler or appliance. Each boiler needs its own vent.
- Inspect the finished vent and air piping for airtightness and compliance with the manual and codes.
- Verify all air openings are correctly sized, unobstructed, and free of airborne contaminants.
- Do not cover nonmetallic vent pipe with thermal insulation.
- Install a vent manufacturer's bird screen at each termination.
- Use sweep elbows on all vent and air piping. Do not use short-radius elbows.
- Use only the vent and air materials listed in this manual.
Applies to: All SVF 500/600 venting and combustion air installations
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SVF 500/600 Series 1 Boiler Manual, p. 29. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.