Viessmann · Boiler troubleshooting

Check the room temperature sensor

Vitotronic 300-K MW1S

What is going on

Use this check when the room temperature shown on the display seems wrong and the remote Vitotrol cannot be used.

Likely causes

  • Sensor reading differs clearly from the actual room temperature
  • Wiring or installation position is causing a wrong reading

Check in this order

  1. Disconnect the wires from the sensor.
  2. Measure the sensor resistance at terminals 9 and 13b.
  3. Compare the resistance with the table for the actual room temperature.
  4. Compare the reading with the room temperature shown on the display (see scan page 91).
  5. Check the installation and replace the sensor if the deviation is severe.

Applies to: Room temperature sensor part no. 7408 012

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 300-K MW1S installation and service instructions, p. 136. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.