Viessmann · Boiler troubleshooting

Replacing the burner door

Vitocrossal 200 CM2

What is going on

Removes the fan, venturi, gas train and burner control from the burner door, then swaps the door. Leak test the gas line after reconnecting it.

Check in this order

  1. Loosen the retaining clamp and disconnect the combustion air flex hose; set it aside.
  2. Disconnect the gas line.
  3. Disconnect electrical plugs 35, 36, 87, 111 and 122 from the burner control. Remove the burner control cover (see p. 30) to reach plugs 87 and 111.
  4. Disconnect plugs 100 and 100A from the fan. Disconnect pressure switch tubes APS1 from the venturi and APS2 from the burner door.
  5. Remove the four M8 (13 mm hex) nuts holding the fan to the burner door. Remove the fan/venturi/gas train assembly and set it aside.
  6. Remove the two M6 bolts and the burner control assembly.
  7. Remove the ignition and ionization electrode block (see p. 36).
  8. Remove the cotter pins and hinge pins from the burner door.
  9. Remove the four M12 (19 mm hex) burner door bolts and washers.
  10. Disconnect plugs 40/156 and 40 from the burner control bracket, and plugs 90 and 41 from the burner control. Replace the barb fitting washer if needed.
  11. Remove the burner tube (see p. 39).
  12. Install the new burner door and attach the door studs for the fan/venturi assembly.
  13. Torque the M8 nuts to 53 lb.in (6 Nm) and the M12 door bolts to 13 lb.ft (18 Nm).
  14. Reinstall in reverse order and leak test the reconnected gas line.

Applies to: Vitocrossal 200 CM2 186 to 311 burner door

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 200 CM2 186 to 311 Service Instructions, p. 40. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.