Weil-McLain · Boiler troubleshooting

SVF ignition sequence and manual reset limits

SVF Series 1SVF Series 2

What is going on

How the SVF lights, so you can see where it stops. Once ignition starts it runs through to main flame even if the heat call ends.

Likely causes

  • Air pressure switch stuck closed before start or not closing with the blower
  • No flame signal within 4 seconds of the gas valves opening
  • A manual reset limit tripped: flame safeguard, high or low gas pressure, high temperature, stack temperature or low water

Check in this order

  1. On a heat call the control first checks the air pressure switch is open (no airflow).
  2. The blower ramps to pre-start speed. When the air switch closes, pre-purge starts, then the blower goes to ignition speed.
  3. Trial for ignition a flame must be seen within 4 seconds after the gas valves open (7 seconds total).
  4. After lighting it holds low fire for the CH low fire hold time, then modulates.
  5. If a manual reset limit trips, find and fix the cause before resetting. Never jumper a safety limit.
  6. If overheating happens or the gas will not shut off, shut the gas off outside the boiler. Do not cut power to the pump.

Applies to: SVF 725, 850, 1000 (Series 1) and SVF 1500-3000 (Series 2)

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain SVF 725/850, 1000 Series 1 / 1500-3000 Series 2 Advanced Installation Manual 550-143-071/0924, Sequence of operations Figure 11, p.11; safety p.3. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.