Weil-McLain · Boiler troubleshooting
SVF ignition sequence and manual reset limits
What is going on
How the SVF lights, so you can see where it stops. Once ignition starts it runs through to main flame even if the heat call ends.
Likely causes
- Air pressure switch stuck closed before start or not closing with the blower
- No flame signal within 4 seconds of the gas valves opening
- A manual reset limit tripped: flame safeguard, high or low gas pressure, high temperature, stack temperature or low water
Check in this order
- On a heat call the control first checks the air pressure switch is open (no airflow).
- The blower ramps to pre-start speed. When the air switch closes, pre-purge starts, then the blower goes to ignition speed.
- Trial for ignition a flame must be seen within 4 seconds after the gas valves open (7 seconds total).
- After lighting it holds low fire for the CH low fire hold time, then modulates.
- If a manual reset limit trips, find and fix the cause before resetting. Never jumper a safety limit.
- If overheating happens or the gas will not shut off, shut the gas off outside the boiler. Do not cut power to the pump.
Applies to: SVF 725, 850, 1000 (Series 1) and SVF 1500-3000 (Series 2)
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Weil-McLain SVF 725/850, 1000 Series 1 / 1500-3000 Series 2 Advanced Installation Manual 550-143-071/0924, Sequence of operations Figure 11, p.11; safety p.3. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.