Choose and prepare the boiler room
What is going on
Boiler room air must be clean, unrestricted and never under negative pressure. Exhaust, attic or dryer fans can pull air faster than the structure can supply it for combustion.
Check in this order
- Place the boiler near an outside wall so fresh air can be ducted to it.
- Do not use exhaust fans in the boiler room or install the boiler near refrigeration equipment.
- Keep the boiler away from stored chemicals and aggressive vapors such as bleach, hair spray, methyl chloride, carbon tetrachloride or perchloroethylene, and away from high dust or humidity.
- Set the boiler on floor able to carry its filled weight, without blocking combustion or ventilation air circulation.
- Never cover the boiler or the combustion air opening, and never store debris near it.
- Place the boiler in a heated indoor space near a floor drain and as close to the chimney or vent as possible.
- Use a concrete foundation if the floor may flood, is not level, or the boiler is in a residential garage. In a garage, raise the burner at least 18 in (457 mm) above the floor.
- Check local authority and gas utility requirements for combustion air.
Applies to: VR1 22 to 33, 91 to 140
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitorond 100 installation and service manual, p. 9. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.