Viessmann · Boiler troubleshooting
Burner does not switch on (multi-boiler)
What is going on
Boiler is requested but the burner does not fire.
Likely causes
- Heating program 9 is set (its button is lit)
- Vitoair draught stabilizer defective (pressure jet burner boilers only)
- Motor-controlled flue gas damper failed (gas boilers with atmospheric burner only)
- Fault on the control unit
- No fuel: oil or LPG supply empty, or natural gas valve closed
Check in this order
- Set the rw heating program (see page 6).
- If the Vitoair is faulty, inform the heating contractor. To run it in manual, press in rotary knob A on the motor and turn it fully beyond setting 4.
- If the flue gas damper has failed, inform the heating contractor. To run it in manual, press in rotary knob A on the motor and turn it fully beyond setting 4.
- If there is a control unit fault, consult the heating contractor. Only then turn emissions test switch S to h with the cover left open.
- Oil or LPG check the fuel supply and reorder if needed. Natural gas: open the gas shut-off valve or contact the gas supplier.
Applies to: Multi-boiler systems
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 100, GC1 operating instructions, p. 15. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.