Viessmann · Boiler troubleshooting

System version 9: heating circuit and one low temperature circuit with motorized isolation valve

Vitotronic 100 GC1Vitocontrol-S VD2/CT3/CM2

What is going on

Vitocrossal 200 (CM2) with Vitotronic 100 GC1 boiler control, Vitocontrol-S (VD2/CT3/CM2) system control, a DHW tank, a mixing valve circuit, and a motorized isolation valve A1. Outdoor reset and load-dependent sequential control with two-stage or modulating burners. The LON-BUS sets the boiler supply temperature from the highest mixing-circuit demand plus an adjustable differential. Codings must be set on every Vitotronic 100 GC1.

Check in this order

  1. Set the Vitotronic 100 GC1 coding as listed in the system version 9 table.
  2. Set the Vitocontrol-S coding as listed in the system version 9 table, including 3C: 0 for condensing strategy.

Applies to: System version 9 (Vitocrossal 200 CM2)

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 100 GC1 and Vitocontrol-S VD2/CT3/CM2 installation and service instructions, p. 28-30. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.