Turn gas on or off to the appliance

I-Series Plus

What is going on

The boiler has no pilot. It uses direct ignition and lights the burner automatically. The manual gas valve at the inlet is turned by hand only.

Likely causes

  • Gas leak or unsafe ignition if steps are skipped

Check in this order

  1. Set the temperature controller to its lowest setting.
  2. Turn off all electric power to the appliance if service is needed.
  3. Turn the manual gas valve at the boiler inlet clockwise to OFF.
  4. To restore gas, wait five minutes to clear any gas, then smell near the floor for gas. If gas is smelled, stop and follow the gas leak procedure.
  5. Turn the manual gas valve counterclockwise to ON by hand only. Do not use tools.
  6. Turn on electric power and set the temperature controller to the desired setting.
  7. If the boiler will not run, turn the gas off again and call a service technician.

Applies to: Manual gas shutoff valve at boiler inlet

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Rinnai I-Series Plus IP060160C installation manual, p. 48. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.