Install boiler pressure relief and air vent
What is going on
Set up the safety header and discharge piping on the boiler.
Check in this order
- Apply pipe sealant to both ends of fittings B, D, F and G and install onto coupling A and tees C.
- Install the pressure relief valve and the air vent, then tighten.
- Run the relief discharge pipe to a floor drain and end it about 6 in. (150 mm) above the drain.
- Do not install a shutoff valve in the discharge pipe, do not reduce its diameter, and do not pipe it to outdoors.
- Keep the discharge pipe end unthreaded and oriented to prevent scalding.
Applies to: All models
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 300 CU3A installation instructions, p. 16. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.