Rapid cycling: boiler turns on and off frequently

CGaCGiEGPEGLGB Series 2LGB Series 3

What is going on

Boiler short-cycles. Usually a thermostat placement, control setting or water flow problem.

Likely causes

  • Thermostat on a wall exposed to drafts or heat sources
  • Thermostat heat anticipator set incorrectly
  • Limit setting too low (steam boiler)
  • Insufficient water flow through boiler

Check in this order

  1. Move thermostat to an inner wall away from heat sources and drafts
  2. Adjust thermostat heat anticipator per the thermostat maker's instructions
  3. On a steam boiler, set the limit to suit the system (maximum 220°F); raise the limit to reduce cycling
  4. Check all valves to and from the boiler and return them to the proper setting
  5. Confirm the circulator is correctly sized

Applies to: All listed CGa, CGi, EG, PEG and LGB boilers

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain CGa, CGi, EG, PEG & LGB user manual, p. 9. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.