CSD-1 fixed high limit test (fault simulation #1 and #2)

Vitodens 200-W B2HB

What is going on

Field test of the fixed high limit as required by CSD-1 where the law requires it. Viessmann is not responsible for any overheating damage caused by this test. Simulation #1 uses the coding card and the flow switch, simulation #2 uses the relay test.

Check in this order

  1. Simulation #1: close the boiler valve and jumper across the flow switch.
  2. Simulation #1: run the boiler at high fire by setting coding address 06 to maximum on B2HB models.
  3. Simulation #1: let the temperature keep rising until the fixed high limit trips, then slowly open the boiler valve to cool the boiler.
  4. Simulation #2: throttle the boiler valve until the burner runs with as little flow as possible.
  5. Simulation #2: run the boiler to high fire using the relay test.
  6. Simulation #2: when the burner shuts down on the electronic limit, close the ball valve to stop the flow.
  7. Simulation #2: confirm the temperature keeps rising until the fixed high limit trips, then slowly open the valve to cool the boiler.
  8. Simulation #3: remove one wire from the limit switch. This creates a control fault that needs a manual reset.

Applies to: Vitodens 200-W B2HB boilers

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitodens 200-W B2HB 19 to 35, 68 to 125 Service Instructions, p. 8. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.