Viessmann · Boiler troubleshooting

Check flue side gaskets and seals

Vitocrossal 200 CM2

What is going on

Check the flue gas collector seal to the boiler. Leaks show as condensate on the outside of the collector.

Likely causes

  • Loose flue gas collector fasteners
  • Damaged gasket

Check in this order

  1. Remove rear panels and disconnect the venting from the flue gas collector.
  2. Check that flue gas collector C is tight to boiler A. Retighten mounting fasteners D if needed.
  3. Reconnect the venting with the flue gas pipe adaptor and tighten with gear clamps.
  4. Check the flue coupling for leaks with a certified leak detector.
  5. Check seals under full load with an inspection mirror if needed.

Applies to: Vitocrossal 200 CM2 186 to 311

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 200 CM2 186 to 311 Service Instructions, p. 21. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.