Boiler control housing installation

Vitorond 200VD2

What is going on

Mount the control housing on the side panel and route capillaries and the boiler sensor away from heat sources. Electrical connections are covered in the boiler control instructions.

Check in this order

  1. Drill four 3 mm holes in side panels A and B as shown. Use a mirror image for left-side mounting.
  2. Punch a 22 mm (7/8 in.) opening in the side panel.
  3. Install the control harness bracket with supplied 8-32 self-tapping screws.
  4. Install the burner harness bracket with the two supplied screws.
  5. Install the top mounting hole cover with two supplied self-tapping screws.
  6. Remove the two plugs on the back of the control housing with a flathead screwdriver, then mount the housing on the side panel.
  7. Secure the control housing with the two supplied screws.
  8. Run the capillaries and boiler temperature sensor through the 22 mm opening and push them as far as possible into the sensor well.
  9. Keep cabling and capillaries away from high heat sources such as the vent, chimney or supply/return piping.
  10. Follow the boiler control installation instructions for electrical connections.

Applies to: Vitorond 200 VD2 boiler control housing

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitorond 200 VD2 installation manual, p. 31-32. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.