Viessmann · Boiler troubleshooting

Checking and cleaning the burner tube

Vitocrossal 300 CA3B

What is going on

Service procedure for inspecting and cleaning the burner tube and burner gauze assembly. Work only on a cold system with the gas shut-off closed.

Check in this order

  1. Dismantle the burner (see the burner dismantling section, p. 70).
  2. Undo the 6 screws from the insulation ring. Torque on reinstall: 13 lb.in (1.5 Nm).
  3. Remove the insulation ring.
  4. Unscrew the burner gauze assembly. Vacuum it or replace it. Torque on reinstall: 7.5 lb.ft (10 Nm).
  5. Replace all gaskets. Reassemble the burner tube and burner in reverse order. Torque: 7.5 lb.ft (10 Nm).
  6. Keep insulation fibres away from the burner tube and out of the combustion chamber when fitting a new tube.

Applies to: Vitocrossal 300 CA3B Series 2.5 to 6.0

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann Vitocrossal 300 CA3B service instructions, p. 72. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.