Viessmann · Boiler troubleshooting
Carry out a LON participant check
What is going on
The participant check tests communication between the fault manager and the devices connected to it.
Likely causes
- Communication not established between the two devices
Check in this order
- Confirm the control is coded as fault manager (coding 79 : 1).
- Confirm the LON participant number is coded in all control units.
- Confirm the fault manager participant list is current.
- Press the two buttons together for about 2 seconds to open the participant check.
- Select the participant with the arrow buttons.
- Start the check. The display and button lights of that participant flash for about 60 seconds.
- If Check not OK appears, check the LON connection and coding.
- Repeat for other participants, then press the two buttons together for about 1 second to exit.
Applies to: Vitotronic 300-K, MW1S
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Viessmann Vitotronic 100/300-K installation and service manual, p. 76. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.