Viessmann · Boiler troubleshooting

Test fixed high limit (simulation #1, pump unplugged)

Vitodens 200-W B2HA

What is going on

Field test of the manual reset high limit. Only do this where required by law, and the manufacturer is not responsible for damage from overheating during this test.

Check in this order

  1. Make sure the boiler and boiler pump are in normal condition. Pump output sÖ is the boiler pump.
  2. Remove the cover from the back of the boiler control to reach the control plugs.
  3. In the extended menu, select Test mode, then flue gas test ON, and press OK.
  4. Wait for the burner to fire and go to high fire.
  5. When the burner lights, gently unplug boiler pump plug sÖ from the control board using pliers.
  6. Watch the boiler temperature on the display. It rises, then the burner shuts off.
  7. The temperature should keep rising to 210°F (99°C) and the high limit should trip with an F2 fault.
  8. If the limit is not reached, repeat the test. Two minutes after the burner shuts off, plug the pump in for a maximum of 1 second.

Applies to: Vitodens 200-W B2HA 45, 60. On boilers 19 to 100 with flow switches, jumpering the flow switches may be needed during testing.

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitodens 200-W B2HA 45, 60 Service Instructions, p. 8. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.