Nothing Happens When DHW Water Flow Is Activated (Combi Only)
What is going on
No burner firing when hot water is drawn, with no code shown.
Likely causes
- Flow below minimum needed to fire
- Flow control sensor faulty
- Clogged inlet water filter
- Hot and cold lines reversed on new installs
- Inlet water too hot
- Integrated boiler pump not operating
- DHW operation switch off
Check in this order
- Verify the minimum flow rate to fire the boiler is reached.
- Measure the resistance of the flow control sensor (see Electrical Diagnostics).
- Clean the inlet water supply filter.
- On new installs, confirm hot and cold lines are not reversed.
- Confirm the inlet water temperature is not too high.
- Confirm the integrated boiler pump operates properly.
- Confirm the DHW operation switch is on.
Applies to: I-Series Plus combi boiler
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Rinnai I-Series Plus IP060160C installation and operation manual, p. 116. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.