Rinnai · Boiler troubleshooting

Nothing Happens When DHW Water Flow Is Activated (Combi Only)

I-Series Plus

What is going on

No burner firing when hot water is drawn, with no code shown.

Likely causes

  • Flow below minimum needed to fire
  • Flow control sensor faulty
  • Clogged inlet water filter
  • Hot and cold lines reversed on new installs
  • Inlet water too hot
  • Integrated boiler pump not operating
  • DHW operation switch off

Check in this order

  1. Verify the minimum flow rate to fire the boiler is reached.
  2. Measure the resistance of the flow control sensor (see Electrical Diagnostics).
  3. Clean the inlet water supply filter.
  4. On new installs, confirm hot and cold lines are not reversed.
  5. Confirm the inlet water temperature is not too high.
  6. Confirm the integrated boiler pump operates properly.
  7. Confirm the DHW operation switch is on.

Applies to: I-Series Plus combi boiler

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Rinnai I-Series Plus IP060160C installation and operation manual, p. 116. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.