CSD-1 field test of fixed high limit switch
What is going on
Where required by law, this test simulates a fixed high limit trip. The fixed high limit needs a manual reset of the boiler control once it trips. Viessmann is not responsible for damage caused by overheating the system during this test.
Check in this order
- Run the boiler to high fire using the relay test.
- Throttle the boiler valve until the burner runs with as little flow as possible.
- When the burner shuts down on the electronic limit, close the ball valve to stop the flow.
- Let the boiler temperature keep rising until the fixed high limit trips.
- After the fixed high limit has tripped, slowly open the boiler valve to cool the boiler down.
- Reset the boiler control manually.
Applies to: Vitocrossal 300 CU3A boilers, where CSD-1 testing is required
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Viessmann Vitocrossal 300 CU3A 26 to 199 service instructions, p. 7. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.