Viessmann · Boiler troubleshooting

Commissioning when system is not filled with softened water

Vitocrossal 300 CA3B Dual Fuel

What is going on

If the system is filled with water that meets the hardness table but is not fully softened, start up gently to limit scale on the heating surfaces.

Check in this order

  1. Start the system step by step with a high heating water flow rate, starting at the lowest boiler output.
  2. In multiple boiler systems, start all boilers at the same time so scale does not collect in one boiler.
  3. Treat the first fill with water treatment before start-up, and do the same for any later filling or top-up.
  4. Check, clean and activate filters, dirt traps and separators after commissioning and in new installations.
  5. Under expansion or repair, drain only the pipework sections that are necessary.

Applies to: Vitocrossal 300 CA3B Dual Fuel 2.5 to 6.0

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0 service instructions, p. 13. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.