Viessmann · Boiler troubleshooting

Connect compiled failure alarm indicator (CM2)

Vitotronic 100

What is going on

Alarm output for a visual and/or audible device. Rated 120 VAC, 60 Hz, maximum 2 FLA. Use AWG 14 wire.

Check in this order

  1. Disconnect power to the control and burner.
  2. Connect the alarm device to the terminal strip in the boiler control connection enclosure as shown in the diagram.
  3. Use a visual and/or audible alarm device rated 120 VAC.

Applies to: CM2 control

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 100 GC1 installation and service instructions, p. 77. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.