What is going on

Venting must be short and straight with a supported horizontal run. Use the factory vent adaptor on the flue gas collar.

Check in this order

  1. Route the vent the shortest way with the fewest elbows. Rearrange water piping if needed for a closer chimney connection.
  2. Support horizontal runs so they do not sag, and avoid long horizontal runs.
  3. Give horizontal runs at least 1/4 in rise per ft from the boiler to the vent terminal.
  4. Strap horizontal runs every 4 ft (1.2 m) with metal strapping.
  5. Attach the factory vent pipe adaptor to the flue gas collar with three equally spaced corrosion resistant self-tapping screws and high temperature silicone, or equivalent.
  6. Connect the chimney through a field supplied 18 in (457 mm) long, slightly inclined intermediate section of 5 in outside diameter flue pipe.
  7. Drill a 1/2 in opening on the side of the vent pipe, about three times the vent pipe diameter from the flue collar, for flue gas analysis.
  8. Seal all flue pipe joints.
  9. Insulate any uninsulated vent pipe to reduce flue gas cooling and noise.
  10. Install an outside rain cap and use a field supplied M-barometric damper for oil, per the draft control maker's instructions.
  11. In Canada, fit the blocked vent safety switch. For direct vent, follow the separate direct vent instructions.

Applies to: VR1 22 to 33, 91 to 140

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitorond 100 installation and service manual, p. 15. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.