Mixing valve motor rotation check
What is going on
When the mixing valve opens, the supply temperature must rise. If it drops, the motor is turning the wrong way or the valve set is fitted incorrectly.
Likely causes
- Motor turning in the wrong direction
- Mixing valve set incorrectly fitted
Check in this order
- Run the mixing valve open in the actuator test.
- Watch the supply temperature while the valve opens.
- If the temperature falls, check the motor rotation direction.
- Check the mixing valve fitting against the mixing valve installation instructions.
Applies to: Mixing valve heating circuits
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 200 and 300-K Installation and Service Instructions, p. 31. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.