Mount and wire the outdoor temperature sensor
What is going on
Place the sensor where it reads outdoor air and not heat from the building.
Check in this order
- Remove the cover from the outdoor temperature sensor.
- Mount the wall base with the cable entry pointing down.
- Run the cable from the boiler control board to the sensor and connect it to the sensor terminals.
- Mount the sensor 6.6 to 8.2 ft. (2 to 2.5 m) above ground on the north or northwest wall.
- On a multi-storey building, mount it in the upper half of the second floor.
- Keep the sensor away from windows, doors, air vents, and under balconies or gutters.
- Do not cover the sensor with plaster. If the wall is not yet plastered, allow for plaster thickness or remove the sensor before plastering.
- Remove the X3 plug from the control board, attach the sensors, reinsert the X3 plug, then reinstall the control cover.
Applies to: Vitocrossal 300 CU3A 26 to 199
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 300 CU3A installation manual, p. 27. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.