Viessmann · Boiler troubleshooting

Mount and wire the outdoor temperature sensor

Vitocrossal 300 CU3A

What is going on

Place the sensor where it reads outdoor air and not heat from the building.

Check in this order

  1. Remove the cover from the outdoor temperature sensor.
  2. Mount the wall base with the cable entry pointing down.
  3. Run the cable from the boiler control board to the sensor and connect it to the sensor terminals.
  4. Mount the sensor 6.6 to 8.2 ft. (2 to 2.5 m) above ground on the north or northwest wall.
  5. On a multi-storey building, mount it in the upper half of the second floor.
  6. Keep the sensor away from windows, doors, air vents, and under balconies or gutters.
  7. Do not cover the sensor with plaster. If the wall is not yet plastered, allow for plaster thickness or remove the sensor before plastering.
  8. Remove the X3 plug from the control board, attach the sensors, reinsert the X3 plug, then reinstall the control cover.

Applies to: Vitocrossal 300 CU3A 26 to 199

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 300 CU3A installation manual, p. 27. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.