Solvent-cement joint method for PVC/CPVC/ABS vent and air piping
What is going on
Joint procedure from the vent and air piping section. Pipe must be clean, dry and dry-fit before any cement is used.
Check in this order
- Cut pipe to length and deburr inside and outside of each pipe end.
- Chamfer the outside of each pipe end so cement spreads evenly.
- Clean all pipe ends and fittings, then dry them thoroughly.
- Dry-assemble the whole vent or air run before cementing any joint.
- Handle fittings and pipe carefully so surfaces stay clean.
- Apply primer generously to both the pipe end and the fitting socket.
- While the primer is still damp, apply approved cement to both surfaces in an even coat.
- Apply a second coat to both surfaces, but do not use so much cement that it builds up inside the pipe.
- While the cement is wet, push the pipe fully into the fitting with a quarter turn.
- Wipe excess cement and confirm a smooth bead shows all around the joint.
Applies to: Ultra vent and air piping
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Weil-McLain Ultra Series 4 boiler manual, p. 90. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.