Weil-McLain · Boiler troubleshooting

Zoning with zone valves: two space heating zones

ECO Tec Series 3

What is going on

Two space heating zones with no Indirect DHW, using zone valves and a system circulator. Shown for Heating Only models. The system must have a by-pass pressure regulating valve, because flow can occur with the zone valves closed.

Check in this order

  1. Wire the zone thermostats to INPUT 2, 3 and 4. INPUT 1 is reserved for the system circulator setup.
  2. Wire Zone 1 and Zone 2 zone valves to Outputs 2 and 3, and the system circulator to Output 1 (2.2 A max).
  3. On Combi models, assign INPUT 2 (not INPUT 1) to AUX PUMP/OUTPUT, and the wiring for J17-4/5 applies.
  4. Assign INPUT 1 (INPUT 2 on Combi) to AUX PUMP/OUTPUT, then select INPUTS PRIORITY SETTING when prompted for when to activate the output.
  5. Confirm that PRIORITY 2 RUN AUX PUMP/OUT is set to YES so the system pump runs when either zone calls for heat.
  6. Set the space heating system type in PRIORITY 2 to match the heating system.
  7. Do not use a wired connection at INPUT 1 (J17-1/2), because it is used for the system circulator control.

Applies to: ECO Tec Series 3 Heating Only models

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: ECO Tec Series 3 boiler manual, p. 76. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.