Zoning with zone valves: two space heating zones
What is going on
Two space heating zones with no Indirect DHW, using zone valves and a system circulator. Shown for Heating Only models. The system must have a by-pass pressure regulating valve, because flow can occur with the zone valves closed.
Check in this order
- Wire the zone thermostats to INPUT 2, 3 and 4. INPUT 1 is reserved for the system circulator setup.
- Wire Zone 1 and Zone 2 zone valves to Outputs 2 and 3, and the system circulator to Output 1 (2.2 A max).
- On Combi models, assign INPUT 2 (not INPUT 1) to AUX PUMP/OUTPUT, and the wiring for J17-4/5 applies.
- Assign INPUT 1 (INPUT 2 on Combi) to AUX PUMP/OUTPUT, then select INPUTS PRIORITY SETTING when prompted for when to activate the output.
- Confirm that PRIORITY 2 RUN AUX PUMP/OUT is set to YES so the system pump runs when either zone calls for heat.
- Set the space heating system type in PRIORITY 2 to match the heating system.
- Do not use a wired connection at INPUT 1 (J17-1/2), because it is used for the system circulator control.
Applies to: ECO Tec Series 3 Heating Only models
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: ECO Tec Series 3 boiler manual, p. 76. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.