Safety connections (Vitotronic control)

Vitorond 100VR1

What is going on

Install the return water injector combination and the pressure relief valve. Minimum pressure relief valve and discharge pipe size is 3/4 in. The boiler does not require a flow switch.

Check in this order

  1. Install the bushing and return water injector combination.
  2. Pipe the pressure relief valve to the boiler water supply connection as illustrated.
  3. Fit the discharge pipe ending about 6 in. (150 mm) above a floor drain, unthreaded.
  4. Do not install an isolation valve between the boiler and the relief valve.
  5. Remove air from the system through the air vents in the system supply.

Applies to: Vitotronic safety connections

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitorond 100 VR1 installation and service manual, p. 20. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.