Viessmann · Boiler troubleshooting
Safety connections (Vitotronic control)
What is going on
Install the return water injector combination and the pressure relief valve. Minimum pressure relief valve and discharge pipe size is 3/4 in. The boiler does not require a flow switch.
Check in this order
- Install the bushing and return water injector combination.
- Pipe the pressure relief valve to the boiler water supply connection as illustrated.
- Fit the discharge pipe ending about 6 in. (150 mm) above a floor drain, unthreaded.
- Do not install an isolation valve between the boiler and the relief valve.
- Remove air from the system through the air vents in the system supply.
Applies to: Vitotronic safety connections
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitorond 100 VR1 installation and service manual, p. 20. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.