Checking the tank and outlet temperature sensors

Vitodens 100-W B1HE/B1KE

What is going on

Resistance check of the DHW tank and outlet temperature sensors.

Check in this order

  1. Check the lead and plug of the tank or outlet temperature sensor.
  2. Disconnect the wires from the sensor plug.
  3. Check the sensor resistance against the curve for the current temperature.
  4. If the deviation is severe (over 10%), replace the sensor.

Applies to: Tank and outlet temperature sensors

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann Vitodens 100-W B1HE/B1KE installation/service manual, p. 83. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.