Viessmann · Boiler troubleshooting
Checking the tank and outlet temperature sensors
What is going on
Resistance check of the DHW tank and outlet temperature sensors.
Check in this order
- Check the lead and plug of the tank or outlet temperature sensor.
- Disconnect the wires from the sensor plug.
- Check the sensor resistance against the curve for the current temperature.
- If the deviation is severe (over 10%), replace the sensor.
Applies to: Tank and outlet temperature sensors
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Viessmann Vitodens 100-W B1HE/B1KE installation/service manual, p. 83. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.