Weil-McLain · Boiler troubleshooting

Vertical concentric termination: roof clearances and multiple boilers

Ultra Series 4

What is going on

The vent outlet must sit at least 6 ft from adjacent walls and 5 ft below a roof overhang, and at least 7 ft above a public walkway. Keep it at least 3 ft above any forced air intake within 10 ft, and at least 12 in below or horizontally from any door, window or gravity air inlet. The air inlet must be at least 12 in above the roof or snow line (18 in in Canada). Keep it at least 4 ft horizontally from any meter, regulator or relief valve. Do not connect other appliances to the vent, and do not tie multiple boilers into one vent pipe.

Check in this order

  1. Verify each clearance from the list before cutting the roof.
  2. When several Ultra boilers share a roof, set all vent outlets at the same height.
  3. Place roof penetrations so there is at least 12 in between centers of adjacent boiler vent pipes (US installations).
  4. For Canadian installs, follow the clearances in CSA B149.1 or B149.2.

Applies to: Vertical 3 in or 4 in concentric vent/air termination

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Ultra Series 4 boiler manual, p. 75-76. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.