The relief valve is required by ANSI Z21.13 and the ASME Boiler and Pressure Vessel Code. It must be accessible for service. An ASME 30 PSI valve is supplied with the boiler.

Check in this order

  1. Fit the relief valve before any shut-off valve in the system.
  2. Make sure the valve meets ANSI Z21.22, CAN1-4.4 and/or ASME Section IV as applicable.
  3. Pipe the central heating relief valve for up to 30 PSI, rated for at least the boiler's maximum Btu/hr.
  4. Pipe the domestic hot water relief valve for up to 150 PSI, rated for at least the boiler's maximum Btu/hr.
  5. Pipe the discharge to the ground or a drain per local code. Keep the discharge line pitched downward and end it 6 in (152 mm) above a drain where discharge can be seen.
  6. Make the discharge end plain (unthreaded), at least 3/4 in nominal pipe diameter, and of material rated for water at 180°F (82°C) or higher.
  7. Do not plumb the relief valve into the condensate drain. Drain each one separately.
  8. Do not plug the relief valve, do not add reducers or restrictions to the relief line, and do not place any valve between the relief valve and the boiler.
  9. Protect the valve and discharge line from freezing.
  10. Manually operate the relief valve once a year to check that it works.
  11. If the valve discharges periodically, check for thermal expansion in the closed system and contact the water supplier or plumbing inspector. Do not plug the valve.

Applies to: Relief valves on the CH and DHW circuits

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Rinnai I-Series Plus IP060160C installation and operation manual, p. 59. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.