Viessmann · Boiler troubleshooting

Start-up with antifreeze in the system (flow reading error)

Vitotron 100 VLN2

What is going on

At low ambient start-up with antifreeze, the flow reading can fail. A special start-up procedure warms the fluid so flow can be read.

Likely causes

  • Low ambient temperature at start-up
  • Physical properties of the antifreeze solution

Check in this order

  1. If the flow indicator flickers and the cut-off valves are open, close the OP and TT contacts.
  2. This starts the special start-up procedure automatically.
  3. Wait while the panel alternates parameters with dash marks (-, --, ---).
  4. The procedure ends and normal operation starts once minimum flow is reached.

Applies to: Vitotron 100 VLN2 with antifreeze

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotron 100 VLN2 installation and service instructions, p. 15. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.