Start-up with antifreeze in the system (flow reading error)
What is going on
At low ambient start-up with antifreeze, the flow reading can fail. A special start-up procedure warms the fluid so flow can be read.
Likely causes
- Low ambient temperature at start-up
- Physical properties of the antifreeze solution
Check in this order
- If the flow indicator flickers and the cut-off valves are open, close the OP and TT contacts.
- This starts the special start-up procedure automatically.
- Wait while the panel alternates parameters with dash marks (-, --, ---).
- The procedure ends and normal operation starts once minimum flow is reached.
Applies to: Vitotron 100 VLN2 with antifreeze
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitotron 100 VLN2 installation and service instructions, p. 15. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.