Weil-McLain · Boiler troubleshooting
Example D - field wiring of master and shadow boilers
What is going on
Master boiler runs the system circulator and the shell-side circulator through the Aux output. Zone 1 and Zone 2 connect to the master, Zones 3 to 6 to the shadow boiler. Outdoor air and system supply/return sensors connect to terminal blocks J16/J17 on the master, with sensor commons at the same blocks. The 120 VAC boiler circulator connects through the service switch to the boiler pump output (J4).
Check in this order
- Wire 120 VAC power and ground to the boiler through the service switch.
- Connect the 120 V boiler circulator to the boiler pump output (J4) with a relay if the load exceeds the rating.
- Connect the system circulator (Item 6a) and shell-side circulator (Item 6b) to Aux outputs on the master as shown.
- Wire each zone thermostat (W, R, C) to the TT input and common terminals listed in Table 5.
- Connect outdoor air, system supply and system return sensors to J19 on the master (use the sensor commons as shown).
- Link the master and shadow boilers with the network connection between them.
Applies to: Example D, master and shadow 2 boilers
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Evergreen Series 2 advanced manual, p. 34. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.