Viessmann · Boiler troubleshooting

Participant check (LON communication test)

Versatronik 505 NR2/BACIPVersatronik 505D NR2/BACIP

What is going on

Confirms communication between the boiler controls and the Vitocontrol-S system control, one subscriber at a time.

Check in this order

  1. Confirm the Vitocontrol-S is error manager and each gateway has a unique rotary dial participant number.
  2. Press OK and Menu together for about 2 seconds to open the Service screen.
  3. Arrow down to Service Functions.
  4. Select Subscriber Check if not already highlighted, then press OK.
  5. Arrow up or down to pick a subscriber and press OK. The screen shows whether the check is active and reports OK or not.
  6. If it passes, pick another subscriber and repeat.
  7. Press the return button to exit the subscriber check.

Applies to: Versatronik 505 gateway on Viessmann boiler controls and Vitocontrol-S cascade

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Versatronik 505 and 505D BACnet IP manual, p. 17. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.