Viessmann · Boiler troubleshooting
Participant check (LON communication test)
What is going on
Confirms communication between the boiler controls and the Vitocontrol-S system control, one subscriber at a time.
Check in this order
- Confirm the Vitocontrol-S is error manager and each gateway has a unique rotary dial participant number.
- Press OK and Menu together for about 2 seconds to open the Service screen.
- Arrow down to Service Functions.
- Select Subscriber Check if not already highlighted, then press OK.
- Arrow up or down to pick a subscriber and press OK. The screen shows whether the check is active and reports OK or not.
- If it passes, pick another subscriber and repeat.
- Press the return button to exit the subscriber check.
Applies to: Versatronik 505 gateway on Viessmann boiler controls and Vitocontrol-S cascade
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Versatronik 505 and 505D BACnet IP manual, p. 17. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.