Venting - Category I (chimney) and Category III (positive pressure)

Vitorond 200 VD2A

What is going on

The boiler is approved as a Category I appliance when vented to a chimney, and as a Category III positive pressure non-condensing boiler when using the positive pressure option. Side wall venting is not approved. The chimney must be designed for the low flue gas temperatures, and its size is not set by the vent collar diameter.

Likely causes

  • Chimney lacks sufficient insulation or is oversized, causing corrosive condensation
  • Flue gases cool too quickly in the chimney

Check in this order

  1. Do not use side wall venting.
  2. Design the chimney for the cool flue gases at partial load.
  3. Insulate the chimney connection between the boiler vent collar and chimney.
  4. If the calculated chimney diameter falls between two sizes, select the larger size.
  5. Install a barometric draft regulator in the chimney/vent (Category I).
  6. Vent each boiler individually.
  7. Use AL29-4C stainless steel single-wall vertical venting (UL/ULC listed for Category III) for positive pressure venting.
  8. Make sure the chimney is gas tight for Category III venting.
  9. Follow local codes; in the USA use the National Fuel Gas Code ANSI Z223.1 for gas or NFPA 31 for oil; in Canada use CAN/CSA B149.1 or .2 for gas or CSA B-139 for oil.
  10. Do not stand on the top panel when installing or insulating overhead piping or venting.

Applies to: Vitorond 200 VD2A boilers

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitorond 200 VD2A Technical Data Manual, p. 23-24. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.