Navien · Boiler troubleshooting

Direct vent termination layouts

NCB700

What is going on

Layouts for vertical and horizontal direct vent terminations and for routing intake and exhaust to different locations.

Check in this order

  1. Vertical direct vent follow the dimensions on the figure. It shows 12 in minimum and 36 in minimum dimensions with end caps on the terminations. Confirm against the drawing.
  2. Horizontal direct vent keep at least 12 in horizontal clearance between terminations.
  3. If 12 in horizontal clearance is not possible, keep at least 36 in vertical clearance with the exhaust above the intake. Do not exceed 20 ft total length.
  4. Intake and exhaust may be run to different locations, each with its own end cap.

Applies to: NCB700-190/060, NCB700-190/080, NCB700-240/110, NCB700-240/130, NCB700-250/150

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NCB700 installation and operation manual, pp. 101-102. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.