Weil-McLain · Boiler troubleshooting
Burner short cycles (turns on and off often)
What is going on
The burner keeps starting and stopping on short cycles. On these boilers it is usually the thermostat or the limit setting, not the burner itself.
Likely causes
- Thermostat mounted where heat or drafts hit it
- Thermostat heat anticipator set wrong
- Limit control set too low
Check in this order
- Check where the thermostat is. Move it to an inside wall away from heat sources and cold drafts.
- If the thermostat has a heat anticipator, set it to the measured current draw of the control circuit (see boiler wiring diagram).
- Check the limit setting. Raise it to cut down cycling, but never above 220°F.
Applies to: WTGO-3 to WTGO-9 oil-fired cast iron boilers
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Weil-McLain WTGO Series 4 Boiler Manual 550-142-332/0225, Troubleshooting, p.7. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.