Weil-McLain · Boiler troubleshooting
Thermostat and circulator wiring limits (schematic)
What is going on
Limits on thermostat and circulator wiring shown on the schematic. Exceeding them can damage the control or thermostats.
Check in this order
- Do not supply 24 VAC power to the thermostat circuits.
- If using 3-wire zone valves, use relays to provide dry contacts to the control thermostat terminals.
- Power stealing thermostats R/W contact current max is 120 mA. If more is needed, use the C terminal. Minimum closure voltage is 13.5 V and minimum current is 13.5 mA.
- Powered thermostats on R/C max 750 mA shared by all thermostats.
- Each circulator output (Circulators 1 to 4 and the 120V boiler circulator) is 2.2 A max.
- Use the 3-way valve actuator (C13) on Combi models only.
- On Combi models, do not use Circulator 1 or Circulator 4.
- The control uses a 3 A fuse for the 24 VAC circuit.
Applies to: ECO Tec Series 3 80/110/150/199
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: ECO Tec Series 3 boiler manual, p. 78. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.