Viessmann · Boiler troubleshooting

Check condensate drain and clean condensate trap

Vitodens 200-W B2HA

What is going on

Condensate must drain freely. If it does not, it builds up in the bottom of the boiler and causes a burner shut-down fault.

Likely causes

  • Blocked or debris-filled condensate trap
  • Restricted drain line

Check in this order

  1. Remove retaining clip A from condensate trap B.
  2. Disconnect flexible discharge tubing C from the trap.
  3. Remove the trap from the boiler.
  4. Clean out any debris and refill the trap with water.
  5. Reinstall the trap and secure with clip A.
  6. Reconnect the flexible discharge tubing.
  7. Do not connect drain from other appliances such as water softener backwash.
  8. Keep the air gap and vent between the trap and neutralization unit (if fitted).

Applies to: Vitodens 200-W B2HA 45, 60

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitodens 200-W B2HA 45, 60 Service Instructions, p. 23. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.