Check condensate drain and clean condensate trap
What is going on
Condensate must drain freely. If it does not, it builds up in the bottom of the boiler and causes a burner shut-down fault.
Likely causes
- Blocked or debris-filled condensate trap
- Restricted drain line
Check in this order
- Remove retaining clip A from condensate trap B.
- Disconnect flexible discharge tubing C from the trap.
- Remove the trap from the boiler.
- Clean out any debris and refill the trap with water.
- Reinstall the trap and secure with clip A.
- Reconnect the flexible discharge tubing.
- Do not connect drain from other appliances such as water softener backwash.
- Keep the air gap and vent between the trap and neutralization unit (if fitted).
Applies to: Vitodens 200-W B2HA 45, 60
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitodens 200-W B2HA 45, 60 Service Instructions, p. 23. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.