Viessmann · Boiler troubleshooting
Boiler control is not active (green power LED off)
What is going on
The control shows no power indication.
Likely causes
- Power switch is in the off position
- Main power to the control and heating system is not on
- Fuse on the Vitotronic control has blown
Check in this order
- Set the power switch to the on position.
- Turn on the main power and confirm 120 VAC is supplied to the control receptacle.
- If the fuse has blown, replace it with the same type and rating: F1, T 6.3 A / 250 V, slow blow.
Applies to: Vitotronic 100 KW10B
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 100 KW10B operating manual, p. 8. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.