Viessmann · Boiler troubleshooting

Boiler control is not active (green power LED off)

Vitotronic 100

What is going on

The control shows no power indication.

Likely causes

  • Power switch is in the off position
  • Main power to the control and heating system is not on
  • Fuse on the Vitotronic control has blown

Check in this order

  1. Set the power switch to the on position.
  2. Turn on the main power and confirm 120 VAC is supplied to the control receptacle.
  3. If the fuse has blown, replace it with the same type and rating: F1, T 6.3 A / 250 V, slow blow.

Applies to: Vitotronic 100 KW10B

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 100 KW10B operating manual, p. 8. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.