Viessmann · Boiler troubleshooting

LON bus wiring and cable limits

Vitotronic 300 GW6B

What is going on

LON runs in line topology with a terminator at each end. Use only one cable type per LON.

Check in this order

  1. Use one cable type within one LON.
  2. Allowed on-site cable 2-core CAT5 screened, or JY(St)Y 2 x 2 x 0.8 mm telephone cable.
  3. Use RJ45 connectors. Cores 1 and 2 plus the screen are required. The cores can be swapped.
  4. Direct connection with Viessmann LON cable: line up to 23 ft (7 m).
  5. Installation spacing 23 to 69 ft (7 to 21 m): use the Viessmann LON cable and a LON coupling. Max 3 cables between 2 appliances.
  6. On-site cable with LON plug line up to 3000 ft (900 m), up to 30 participants.
  7. On-site cable with LON junction boxes line up to 3000 ft (900 m).
  8. Fit a terminal end resistor at each end of the line.
  9. Follow the cabling requirements for the FTT 10-A LON interface.

Applies to: Vitotronic 300 GW6B and Vitocom on LON

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 300 GW6B installation and service manual, p. 46. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.