LON bus wiring and cable limits
What is going on
LON runs in line topology with a terminator at each end. Use only one cable type per LON.
Check in this order
- Use one cable type within one LON.
- Allowed on-site cable 2-core CAT5 screened, or JY(St)Y 2 x 2 x 0.8 mm telephone cable.
- Use RJ45 connectors. Cores 1 and 2 plus the screen are required. The cores can be swapped.
- Direct connection with Viessmann LON cable: line up to 23 ft (7 m).
- Installation spacing 23 to 69 ft (7 to 21 m): use the Viessmann LON cable and a LON coupling. Max 3 cables between 2 appliances.
- On-site cable with LON plug line up to 3000 ft (900 m), up to 30 participants.
- On-site cable with LON junction boxes line up to 3000 ft (900 m).
- Fit a terminal end resistor at each end of the line.
- Follow the cabling requirements for the FTT 10-A LON interface.
Applies to: Vitotronic 300 GW6B and Vitocom on LON
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 300 GW6B installation and service manual, p. 46. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.