Zone control wizard setup
What is going on
Run the zone control wizard from the service menu after power-up and clock setting. Pick the number of zone circuits (1, 2 or 3), then set each zone circuit (ZC2 and ZC3 are set in the same way).
Check in this order
- Power on the boiler.
- Set the time and date.
- Press Menu and OK together to open the service menu.
- Press the down arrow to Service Functions and press OK.
- Set Activate to Yes arrow up to YES and press OK.
- Select the number of ZC circuits 1, 2 or 3.
- Press OK on each screen to save and move to the next step.
- Check the zone output summary and press back if it is wrong.
Applies to: Vitocrossal 300 CU3A zone control
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 300 CU3A application guide, p. 20. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.