Viessmann · Boiler troubleshooting

Fixed high limit test (per boiler section)

Vitocrossal 300 CA3B Dual Fuel

What is going on

Each boiler section has its own fixed high limit and each must be tested individually. The test raises the boiler water temperature until the fixed limit trips, so the boiler must be watched closely. Viessmann is not responsible for damage caused by overheating during this test.

Check in this order

  1. Use the emission test switch on the boiler section to start a call for heat.
  2. In menu 6 of that section's burner control (GC310), item 4, temporarily raise the max boiler water temperature to 243°F (117°C) so it is above the fixed limit.
  3. Press the emission test switch for the section so the burner starts.
  4. Slowly throttle the water flow to the boiler.
  5. Watch the temperature on the GW6C service display.
  6. When the fixed high limit trips, the control hard locks out with F F2 displayed. The fan runs for 10 minutes.
  7. Reset the fault only after the water temperature has dropped.
  8. Restore the original menu 6 item 4 setting.

Applies to: Vitocrossal 300 CA3B Dual Fuel 2.5 to 6.0

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0 service instructions, p. 10. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.